Back

WA North Metropolitan Health Service

QEII - G Block Level 3 - AC2 Remediation Works

AwardedSelect Tender

Details

Awarded
Select tender
This is a select tender. Details and access to the source may be limited to invited suppliers only.

Description

AC2 Remediation Works ? Seal and rectify pipework leak above smoke damper control board where required. ? Replace Supply Air - 2 cold duct connections to Air Con - 2 casing and insulate joints. ? Seal floors within all Air Con - 2 chambers with low Volatile Organic Compound (VOC) antimicrobial polyurethane sealant. Priority to seal cold deck floor. ? Install new non-perforated powder coated steel internal cladding to walls and roof of cold deck. All joints to be sealed with anti-microbial silicone sealant. Existing corroded panels to be either removed or treated with corrosion inhibitor coating prior to cladding. ? Replace all existing insulation on Chilled Water pipework internal to the AHU. New insulation to be closed cell polyolefin foam, complete with external vapour barrier. ? Replace corroded filter frames with new GSS frames. ,. : ? Thoroughly clean cooling coils and condensate drip trays and comb out coil fins. - ? Replace coil condensate lines with Polyvinyl chloride (PVC) and ensure PVC tundish is maximum 25mm from outlet. Full internal clean on completion of works using anti-fungal and anti-bacterial cleaner

Request type

Select Tender

TenderHub gathers information continuously from a variety of sources. There may be delays between information being updated at the source and presented here. Always check with the source if you are concerned about currency or accuracy.

Key details

Source
Tenders WA

Briefings & site visits

No briefings or site visits were listed for this tender.

Awarded suppliers

1

Contract awarded

$226,758 awarded to 1 supplier

See who else bid on this tender

Subscribers see every supplier who bid on this tender, plus its change history and a direct link to the source notice.