West Moreton Hospital and Health Service
Air Conditioning Replacement at Dawson House
Details
Description
West Moreton Hospital and Health service are seeking Proposals from a suitably qualified Contractor for WMHHS112458 Air Conditioning Replacement, Dawson House.
It includes the removal and replacement of ceiling mounted units in Dawson House, located at The Park Centre for Mental Health (Wacol QLD 4076).
These goods/services specifically include the Contractor/s to:
- Confirm sizing of existing unit is appropriate and integrity of existing installation, report prior to undertaking modifications.
- Ensure new units are appropriate for reliable operation in 36degC dry bulb and 26.5degC wet-bulb ambient temperatures.
- Upgrade or validate the existing condenser water reticulation to the capacity to deliver 23degC throughout the building at the ambient temperatures nominated above.
- Electrically isolate the existing unit/s.
- Reclaim and dispose of refrigerant as required.
- Remove existing units and dispose of them in an appropriate manner as required.
- Crane hire roof removal and replacement for all units (6 of) in the level 3 roof cavity shall be included in your tender.
- Install new indoor units.
- Supply and install all necessary pipework/duct modifications and wiring as required.
- Supply and install all 240/415V supply cabling and isolators for new units as required
- Supply and install mounting brackets and platforms as required to accommodate and maintain the units.
- Pressurise, leak test and triple evacuate the system/s.
- Test run units and trim refrigerant charge.
- Reconfigure wiring and ensure fire alarm shutdown is operational.
- All wiring and controls to match the configuration of existing units.
- Update BMS controls & Graphics to native BACnet interoperable Siemens or Schneider equipment and commission.
- Fully commission units as per TS 5342:2021
- Provide new filters for all units.
- To complete air balance of system ensuring even supply air temperature to all rooms, 23degrees +or – 1 deg
- Update existing drawings to reflect any changes.
- Provide new traffolyte labels to match existing and reflect unit numbers on drawings.
- Upgrade all flexible ducting with new R2 rated flexible ducting
- Prepare surfaces and apply an anti-microbial coating to all internal ducting (supply & return), cushion headboxes, and dampers.
- Apply Aeris-Guard surface treatment to all supply & return air grilles & boxes.
A site inspection is offered 11 am (AEST) on 22/03/2022 with Tenderers encouraged to attend and must register with [email hidden]
For further information on the inspection and specific goods/services sought, including details of existing units please review "WMHHS112458 Specification Document".
Locations
Categories
Request type
Request for Tender
TenderHub gathers information continuously from a variety of sources. There may be delays between information being updated at the source and presented here. Always check with the source if you are concerned about currency or accuracy.
Key details
- Source
- QLD QTenders
Briefings & site visits
- Inspection
22 March 2022
A site inspection is offered 11 am (AEST) on 22/03/2022 with Tenderers encouraged to attend and must register with [email protected]
Awarded suppliers
1Contract awarded
$448,900 awarded to 1 supplier
SABE Services Group
$0
Unit 20, 5-7 Cairns Street, Loganholme, QLD, Australia, 4129
See who else bid on this tender
Subscribers see every supplier who bid on this tender, plus its change history and a direct link to the source notice.